CVE-2025-7693
Rockwell Automation PLC - Micro850 L50E — Rockwell Automation Micro800 Vulnerability
Description · from the CVE record
A security issue exists due to improper handling of malformed CIP Forward Close packets during fuzzing. The controller enters a solid red Fault LED state and becomes unresponsive. Upon power cycle, the controller will enter recoverable fault where the MS LED and Fault LED become flashing red and reports fault code 0xF015. To recover, clear the fault.
Affected
ProductAffectedFixed inSource
PLC - Micro850 L50EV20.011 - V22.011–CNA
Scores by source
Rockwell (CNA)9.3CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N
CISA ADPSSVCExploitation: none · Automatable: yes · Technical impact: total