CVE-2023-0052
SAUTER Controls Nova 220 (EYK220F001) DDC with BACnet connection — SAUTER Controls Nova 200–220 Series Missing Authentication for Critical Function
Description · from the CVE record
SAUTER Controls Nova 200–220 Series with firmware version 3.3-006 and prior and BACnetstac version 4.2.1 and prior allows the execution of commands without credentials. As Telnet and file transfer protocol (FTP) are the only protocols available for device management, an unauthorized user could access the system and modify the device configuration, which could result in the unauthorized user executing unrestricted malicious commands.
Affected
ProductAffectedFixed inSource
Nova 220 (EYK220F001) DDC with BACnet connectionFirmware all versions – 3.3-006–CNA
Nova 220 (EYK220F001) DDC with BACnet connectionBACnetstac all versions – 4.2.1–CNA
Nova 230 (EYK230F001) DDC with BACnet connectionFirmware all versions – 3.3-006–CNA
Nova 230 (EYK230F001) DDC with BACnet connectionBACnetstac all versions – 4.2.1–CNA
Nova 106 (EYK300F001) BACnet communication cardFirmware all versions – 3.3-006–CNA
Nova 106 (EYK300F001) BACnet communication cardBACnetstac all versions – 4.2.1–CNA
moduNet300 (EY-AM300F001, EY-AM300F002)Firmware all versions – 3.3-006–CNA
moduNet300 (EY-AM300F001, EY-AM300F002)BACnetstac all versions – 4.2.1–CNA
Scores by source
icscert (CNA)9.8CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
CISA ADPSSVCExploitation: none · Automatable: yes · Technical impact: total